Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search

is complete.

n

b5-01: PID Function Setting

Enables and disables the PID operation and selects the PID operation mode.

No.

Parameter Name

Setting Range

Default

b5-01

PID Function Setting

0, 1

1

Setting 0: PID disabled
Setting 1: Output frequency = PID output 1

The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.

n

C1-01 to C1-04: Accel, Decel Times 1 and 2

Two different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched

automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).

Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02

are the default active accel/decel settings.

No.

Parameter Name

Setting Range

Default

C1-01

Acceleration Time 1

0.0 to 6000.0 s

<1>

20.0 s

C1-02

Deceleration Time 1

10.0 s

C1-03

Acceleration Time 2

C1-04

Deceleration Time 2

<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time

is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.

Switching Acceleration Times by Digital Input

Accel/decel time 1 is active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs

(H1-oo = 7 and 1A) as explained in

Table i.21

.

Table i.21 Accel/Decel Time Selection by Digital Input

Accel/Decel Time Sel. 1

H1-oo = 7

Accel/Decel Time Sel. 2

H1-oo = 1A

Active Times

Acceleration

Deceleration

0

0

C1-01

C1-02

1

0

C1-03

C1-04

Figure i.39

shows an operation example for changing accel/decel times. The example below requires that the stopping method

be set for “Ramp to stop” (b1-03 = 0).

Output

frequency

Accel Time 1

(C1-01)

Decel Time 1

(C1-02)

Accel Time 2

(C1-03)

Decel Time 2

(C1-04)

Decel Time 1

(C1-02)

Time

FWD (REV)

Run command

ON

OFF

ON

ON

Accel/Decel Time Selection 1

(Terminals S1 to S7, H1-oo = “7”)

OFF

Figure i.39 Timing Diagram of Accel/Decel Time Change