ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 112

Advertising
background image

Diagnostics and Troubleshooting

MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 112 of 199

ProSoft Technology, Inc.

June 18, 2014

Bit

Description

Value

0

Read block start value is greater than the database size.

0x0001

1

Read block start value is less than zero.

0x0002

2

Read block count value is less than zero.

0x0004

3

Read block count + start is greater than the database size.

0x0008

4

Write block start value is greater than the database size.

0x0010

5

Write block start value is less than zero.

0x0020

6

Write block count value is less than zero.

0x0040

7

Write block count + start is greater than the database size.

0x0080

8

0x0100

9

0x0200

10

0x0400

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

The port configuration error words have the following definitions:

Bit

Description

Value

0

Type code is not valid. Enter a value from 0 (Master) to 1
(Slave).

0x0001

1

The float flag parameter is not valid.

0x0002

2

The float start parameter is not valid.

0x0004

3

The float offset parameter is not valid.

0x0008

4

Protocol parameter is not valid.

0x0010

5

Baud rate parameter is not valid.

0x0020

6

Parity parameter is not valid.

0x0040

7

Data bits parameter is not valid.

0x0080

8

Stop bits parameter is not valid.

0x0100

9

Slave ID is not valid.

0x0200

10

Input bit or word, output word and/or holding register
offset(s) are not valid.

0x0400

11

Command count parameter is not valid.

0x0800

12

Spare

0x1000

13

Spare

0x2000

14

Spare

0x4000

15

Spare

0x8000

Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.