Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 143 of 199

June 18, 2014

Note: Terminating resistors are generally not required on the RS-485 network, unless you are

experiencing communication problems that can be attributed to signal echoes or reflections. In

these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module
connector end of the RS-485 line may improve communication quality.

RS-485 and RS-422 Tip

If communication in the RS-422 or RS-485 mode does not work at first, despite
all attempts, try switching termination polarities. Some manufacturers interpret +
and -, or A and B, polarities differently.

6.3.7 DB9 to RJ45 Adaptor (Cable 14)

6.4

MVI56E-MCM Database Definition

This section contains a listing of the internal database of the MVI56E-MCM
module. This information can be used to interface other devices to the data
contained in the module.

Register Range

Modbus Low

Modbus High

Content

Size

0 to 5999

40001

50000

User Data

10000

10000 to 10009

50001

50010

Backplane Configuration

10

10010 to 10039

50011

50040

Port 1 Setup

30

10040 to 10069

50041

50070

Port 2 Setup

30

10070 to 12669

50071

52670

Port 1 Commands

2600

12670 to 15269

52671

55270

Port 2 Commands

2600

15270 to 15359

55271

55350

Misc. Status Data