MVI56E-MCM ♦ ControlLogix Platform

Configuration as a Modbus Slave

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 59 of 199

June 18, 2014

With the sample configuration, the following is the layout of the tags and
addressing.

The sample configuration values configure the module database for
W

RITE

D

ATA

[0

TO

599]

to be stored in the module memory at register 0 to 599,

and R

EAD

D

ATA

[0

TO

599] to be stored in the module memory at registers 1000 to

1599 as shown above.

3.2.1 Modbus Memory Map

Based on the configuration described above, below is the default Modbus
address for the module. Each register within the module can be accessed as a
0xxx bit address, 1xxxx bit address, 3xxxx register address, or 4xxxx register
address.

MVI Address

0xxx

1xxxx

3xxxx

4xxxx

Tag Address

0

0001 to 0016

10001 to 10016 30001

40001

WriteData[0]

1

0017 to 0032

10017 to 10032 30002

40002

WriteData[1]

2

0033 to 0048

10033 to 10048 30003

40003

WriteData[2]

3

0049 to 0064

10049 to 10064 30004

40004

WriteData[3]

4

0065 to 0080

10065 to 10080 30005

40005

WriteData[4]

5

0081 to 0096

10081 to 10096 30006

40006

WriteData[5]

6

0097 to 0112

10097 to 10112 30007

40007

WriteData[6]

7

0113 to 0128

10113 to 10128 30008

40008

WriteData[7]

8

0129 to 0144

10129 to 10144 30009

40009

WriteData[8]

9

0145 to 0160

10145 to 10160 30010

40010

WriteData[9]

10

0161 to 0176

10161 to 10176 30011

40011

WriteData[10]