ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 51

Advertising
background image

MVI56E-MCM ♦ ControlLogix Platform

Configuration as a Modbus Master

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 51 of 199

June 18, 2014

2.4.5 Write to Enron/Daniel Floats

To issue a Write command to Enron/Daniel Floats, use the Float Flag and Float
Start parameters within the ModDef controller tags.

The following table describes the addresses that will be written to by the module.

Address

Data Type

Parameter

47001

32 bit REAL

Demand

47002

32 bit REAL

Reactive Power

47003

32 bit REAL

Apparent Power

47004

32 bit REAL

Power Factor

47005

32 bit REAL

Voltage: Line to Line

47006

32 bit REAL

Voltage: Line to Neutral

47007

32 bit REAL

Current

Configure the Float Start and Float Flag parameters as shown.

The Float Flag causes the module to use the FloatStart parameter to determine
which DevAddress requires a write command to issue double the number of
bytes.

With the above configuration, any DevAddress > 7000 is known to be floating-
point data. Therefore, a count of 1 will send 4 bytes of data, instead of the normal
2 bytes of data to a non Enron/Daniel floating-point register.

1 First, copy the floating-point data from the ControlLogix processor into the

MCM.DATA.W

RITE

D

ATA

array used by the MVI56E-MCM module. Below is

an example.

2 The length of this COP statement must now be 14. This will COP as many of

the MCM_F

LOAT

_D

ATA

values required to occupy the

MCM.D

ATA

.W

RITE

D

ATA

array for a length of 14. This will take 7 registers,

MCM_F

LOAT

_D

ATA

[0]

TO

[6],

and place that data into

MCM.DATA.W

RITE

D

ATA

[0]

TO

[13].

Advertising