MVI56E-MCM ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 77 of 199

June 18, 2014

5.1.2 Non-Scrolling LED Status Indicators

The non-

scrolling LEDs indicate the module’s operating status as follows:

LED Label

Color

Status

Indication

APP

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack. May also be OFF during configuration
download.

GREEN

The MVI56E-MCM is working normally.

RED

The most common cause is that the module has detected a
communication error during operation of an application port.
The following conditions may also cause a RED LED:

The firmware is initializing during startup

The firmware detects an on-board hardware problem
during startup

Failure of application port hardware during startup

The module is shutting down

The module is rebooting due to a ColdBoot or WarmBoot
request from the ladder logic or Debug Menu

OK

Red or
Green

OFF

The module is not receiving adequate power or is not securely
plugged into the rack.

GREEN

The module is operating normally.

RED

The module has detected an internal error or is being
initialized. If the LED remains RED for over 10 seconds, the
module is not working. Remove it from the rack and re-insert it
to restart its internal program.

ERR

Red

Not used.

5.2

Clearing a Fault Condition

Typically, if the OK LED on the front of the module turns RED for more than ten
seconds, a hardware problem has been detected in the module or the program
has exited.

To clear the condition, follow these steps:

1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify that the card is installed

correctly.

5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the

ControlLogix controller.

If the module's OK LED does not turn GREEN, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.