ProSoft Technology MVI56E-MCM/MCMXT User Manual
Page 23

MVI56E-MCM ♦ ControlLogix Platform
Start Here
Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 23 of 199
June 18, 2014
2 Select 1756-MODULE. If you're using a controller revision of 16 or less,
expand O
THER
in the S
ELECT
M
ODULE
dialog box, and then select the 1756-
MODULE.
3 Fill the module properties as follows:
Parameter
Value
N
AME
Enter a module identification string. Example: MCM_2.
D
ESCRIPTION
Enter a description for the module. Example: ProSoft Modbus
Communication Module.
C
OMM
F
ORMAT
Select D
ATA
-INT.
S
LOT
Enter the slot number in the rack where the MVI56E-MCM
module is located.
I
NPUT
A
SSEMBLY
I
NSTANCE
1
I
NPUT
S
IZE
250
O
UTPUT
A
SSEMBLY
I
NSTANCE
2
O
UTPUT
S
IZE
248
C
ONFIGURATION
A
SSEMBLY
I
NSTANCE
4
C
ONFIGURATION
S
IZE
0
4 Click OK
to confirm. The new module is now visible: