ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 23

Advertising
background image

MVI56E-MCM ♦ ControlLogix Platform

Start Here

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 23 of 199

June 18, 2014

2 Select 1756-MODULE. If you're using a controller revision of 16 or less,

expand O

THER

in the S

ELECT

M

ODULE

dialog box, and then select the 1756-

MODULE.

3 Fill the module properties as follows:

Parameter

Value

N

AME

Enter a module identification string. Example: MCM_2.

D

ESCRIPTION

Enter a description for the module. Example: ProSoft Modbus
Communication Module.

C

OMM

F

ORMAT

Select D

ATA

-INT.

S

LOT

Enter the slot number in the rack where the MVI56E-MCM
module is located.

I

NPUT

A

SSEMBLY

I

NSTANCE

1

I

NPUT

S

IZE

250

O

UTPUT

A

SSEMBLY

I

NSTANCE

2

O

UTPUT

S

IZE

248

C

ONFIGURATION

A

SSEMBLY

I

NSTANCE

4

C

ONFIGURATION

S

IZE

0

4 Click OK

to confirm. The new module is now visible: