ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 162

Advertising
background image

Reference

MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 162 of 199

ProSoft Technology, Inc.

June 18, 2014

Because the Slave interface device is serviced at the end of a controller's scan,
data reflects coil status at the end of the scan. Some Slaves limit the quantity of
coils provided each scan; thus, for large coil quantities, multiple PC transactions
must be made using coil status from sequential scans.

Adr Func

Byte
Count

Data Coil
Status 20 to

27

Data Coil
Status 28 to

35

Data Coil
Status 36 to

43

Data Coil
Status 44 to

51

Data Coil
Status 52 to

56

Error
Check

Field

0B

01

05

CD

6B

B2

OE

1B

CRC

The status of coils 20 to 27 is shown as CD(HEX) = 1100 1101 (Binary). Reading
left to right, this shows that coils 27, 26, 23, 22, and 20 are all on. The other coil
data bytes are decoded similarly. Due to the quantity of coil statuses requested,
the last data field, which is shown 1B (HEX) = 0001 1011 (Binary), contains the
status of only 5 coils (52 to 56) instead of 8 coils. The 3 left most bits are
provided as zeros to fill the 8-bit format.

6.8.3 Read Input Status (Function Code 02)

Query
This function allows the user to obtain the ON/OFF status of discrete inputs in the
addressed Slave PC Broadcast mode is not supported with this function code. In
addition to the Slave address and function fields, the message requires that the
information field contain the initial input address to be read (Starting Address)
and the number of locations that are interrogated to obtain status data.

The addressing allows up to 2000 inputs to be obtained at each request;
however, the specific Slave device may have restrictions that lower the maximum
quantity. The inputs are numbered form zero; (input 10001 = zero, input 10002 =
one, input 10003 = two, and so on, for a 584).

The following table is a sample read input status request to read inputs 10197 to
10218 from Slave number 11.

Note: This is the structure of the message being sent out to the Modbus network. The byte values

below are in hexadecimal display.

Adr

Func

Data Start Pt Hi

Data Start Pt Lo Data #of Pts Hi Data #of Pts Lo Error Check Field

0B

02

00

C4

00

16

CRC