background image

MVI56E-MCM ♦ ControlLogix Platform

Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 127 of 199

June 18, 2014

Module Configuration Block (9000)
On boot-up, the module sends a request for configuration information to the
processor. The request block has a Block ID of 9000.

Block Request from Module to Processor

Word Offset

Description

Length

0

Reserved

1

1

9000

1

2 to 248

Spare

247

249

9000

1

The processor responds by sending a block with general configuration
information to the module.

Configuration Block from Processor to Module

Word Offset

Description

Length

0

9000

1

1 to 6

Backplane Setup

6

7 to 31

Port 1 Configuration

25

32 to 56

Port 2 Configuration

25

57 to 59

Port 1 Aux. Configuration

3

60 to 62

Port 2 Aux. Configuration

3

63 to 247

Spare

185

If the configuration information is valid, the module commences normal data
transfer operation. If there are errors in the configuration, the module sends the
processor a read block with configuration error codes.

Block Response from Module to Processor

Word Offset

Description

Length

0

Reserved

1

1

9000

1

2

Module Configuration Error Code

1

3

Port 1 Configuration Error Code

1

4

Port 2 Configuration Error Code

1

5 to 248

Spare

244

249

-2 or -3

1

Any errors must be corrected before the module will start operating.