MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 48 of 199

ProSoft Technology, Inc.

June 18, 2014

Copy data from the MCM.DATA.R

EAD

D

ATA

[0] and [1]

into the tag

E

NERGY

_C

ONSUMPTION

that has a data type of REAL. Use a COP

statement

within the ladder logic. Here is an example.

Because the tag MCM.DATA.R

EAD

D

ATA

[0] should only be used within the above

command, an unconditional COP statement can be used.

Notice the length of the COP statement is a value of 1. Within a Rockwell
Automation processor, a COP statement will copy the required amount of
"Source" values to fill the "Dest" tag for the Length specified.

Therefore, the above statement will copy ReadData[0] and [1] to fill the 32 bits
required for the tag "Energy_Consumption".

Note: Do not use a MOV statement. A MOV will convert the data from the Source register to the

destination register data type. This would create a data casting statement and will result in the loss

or corruption of the original data.

2.4.2 Read Multiple Floating-Point Registers

The following table is an example to read Multiple Floating-Point values and
device addresses. The table shows 7 consecutive floating-point values (14
Modbus addresses).

Value

Description

Type

40261

KW

Demand (power)

Float. upper 16 bits

40263

VAR

Reactive Power

Float. upper 16 bits

40265

VA

Apparent Power

Float. upper 16 bits

40267

Power Factor

Float. upper 16 bits

40269

VOLTS

Voltage, line to line

Float. upper 16 bits

40271

VOLTS

Voltage, line to neutral

Float. upper 16 bits

40273

AMPS

Current

Float. upper 16 bits

Configure the command to read these 7 floats as follows.

Configure an array of 7 floats within the ControlLogix processor as shown in the
following illustration.