5diagnostics and troubleshooting – ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 75

Advertising
background image

MVI56E-MCM ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 199

June 18, 2014

5

Diagnostics and Troubleshooting

In This Chapter

Ethernet LED Indicators ........................................................................ 75

Clearing a Fault Condition ..................................................................... 77

Troubleshooting the LEDs ..................................................................... 78

Setting Up ProSoft Configuration Builder .............................................. 78

Connecting Your PC to the Module ....................................................... 83

Downloading the Project to the Module ................................................. 98

Using the Diagnostics Menu in ProSoft Configuration Builder ............... 99

Reading Status Data from the Module ................................................ 111

Configuration Error Codes ................................................................... 111

Connect to the Module’s Web Page .................................................... 113

The module provides information on diagnostics and troubleshooting in the
following forms:
 LED status indicators on the front of the module provide information on the

module’s status.

 Status data contained in the module can be viewed in ProSoft Configuration

Builder through the Ethernet port.

 Status data values are transferred from the module to the processor.

5.1

Ethernet LED Indicators

The Ethernet LEDs indicate the module's Ethernet port status as follows:

LED

State

Description

Data

OFF

Ethernet connected at 10Mbps duplex speed

AMBER Solid Ethernet connected at 100Mbps duplex speed

Link

OFF

No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.

GREEN Solid
or Blinking

Physical network connection detected. This LED must be ON solid
for Ethernet communication to be possible.