MVI Address

0xxx

1xxxx

3xxxx

4xxxx

Tag Address

50

0801 to 0816

10801 to 10816 30051

40051

WriteData[50]

100

1601 to 1616

11601 to 11616 30101

40101

WriteData[100]

200

3201 to 3216

13201 to 13216 30201

40201

WriteData[200]

500

8001 to 8016

18001 to 18016 30501

40501

WriteData[500]

598

9569 to 9584

19569 to 19584 30599

40599

WriteData[598]

599

9585 to 9600

19585 to 19600 30600

40600

WriteData[599]

600 to 999

N/A

N/A

N/A

N/A

Reserved

1000

31001*

41001

ReadData[0]

1001

31002*

41002

ReadData[1]

1002

31003*

41003

ReadData[2]

1003

31004*

41004

ReadData[3]

1004

31005*

41005

ReadData[4]

1005

31006*

41006

ReadData[5]

1006

31007*

41007

ReadData[6]

1007

31008*

41008

ReadData[7]

1008

31009*

41009

ReadData[8]

1009

31010*

41010

ReadData[9]

1010

31011*

41011

ReadData[10]

1050

31051*

41051

ReadData[50]

1100

31101*

41101

ReadData[100]

1200

31201*

41201

ReadData[200]

1500

31501*

41501

ReadData[500]

1598

31599*

41599

ReadData[598]

1599

31600*

41600

ReadData[599]

The above addressing chart will work with many Modbus applications. Values
listed in the R

EAD

D

ATA

array for 31001 to 31600 are shown with an * beside

them.

Although these are valid addresses, they will not work in the application. The
Master must issue a Write command to the addresses that correspond to the
R

EAD

D

ATA

array. For Modbus addresses 3xxxx these are considered Input

registers, and a Modbus Master does not have a function code for this type of
data.