ProSoft Technology MVI56E-MCM/MCMXT User Manual
Page 18
![background image](/files/866138/content/doc018.png)
Start Here
MVI56E-MCM ♦ ControlLogix Platform
User Manual
Modbus Communication Module
Page 18 of 199
ProSoft Technology, Inc.
June 18, 2014
Parameter
Value
S
LOT
Enter the slot number in the rack where the MVI56E-MCM
module is located
I
NPUT
A
SSEMBLY
I
NSTANCE
1
I
NPUT
S
IZE
250
O
UTPUT
A
SSEMBLY
I
NSTANCE
2
O
UTPUT
S
IZE
248
C
ONFIGURATION
A
SSEMBLY
I
NSTANCE
4
C
ONFIGURATION
S
IZE
0
Important: You must select the C
OMM
F
ORMAT
as D
ATA
-
INT in the dialog box, otherwise the
module will not communicate over the backplane of the ControlLogix rack.
4 Click OK
to continue.
5 Edit the Module Properties.
Select the R
EQUESTED
P
ACKET
I
NTERVA
l value for scanning the I/O on the
module. This value represents the minimum frequency at which the module
will handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.