Parameter

Value

S

LOT

Enter the slot number in the rack where the MVI56E-MCM
module is located

I

NPUT

A

SSEMBLY

I

NSTANCE

1

I

NPUT

S

IZE

250

O

UTPUT

A

SSEMBLY

I

NSTANCE

2

O

UTPUT

S

IZE

248

C

ONFIGURATION

A

SSEMBLY

I

NSTANCE

4

C

ONFIGURATION

S

IZE

0

Important: You must select the C

OMM

F

ORMAT

as D

ATA

-

INT in the dialog box, otherwise the

module will not communicate over the backplane of the ControlLogix rack.

4 Click OK

to continue.

5 Edit the Module Properties.

Select the R

EQUESTED

P

ACKET

I

NTERVA

l value for scanning the I/O on the

module. This value represents the minimum frequency at which the module
will handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.