MVI56E-MCM ♦ ControlLogix Platform

Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 121 of 199

June 18, 2014

Word Offset

Description

Length

209 to 210

Run Number

2

211 to 217

Port 1 Error Status

7

218 to 224

Port 2 Error Status

7

225 to 230

Data Transfer Status

6

231

Port 1 Current Error/Index

1

232

Port 1 Last Error/Index

1

233

Port 2 Current Error/Index

1

234

Port 2 Last Error/Index

1

235 to 248

Spare

14

249

Read Block ID

1

The Read Block ID is an index value used to determine the location of where the
data will be placed in the ControlLogix processor controller tag array of module
read data. Each transfer can move up to 200 words (block offsets 2 to 201) of
data. In addition to moving user data, the block also contains status data for the
module. This last set of data is transferred with each new block of data and is
used for high-speed data movement.

The Write Block ID associated with the block requests data from the ControlLogix
processor. Under normal program operation, the module sequentially sends read
blocks and requests write blocks. For example, if the application uses three read
and two write blocks, the sequence will be as follows:

R1W1

R2W2

R3W1

R1W2

R2W1

R3W2

R1W1

This sequence will continue until interrupted by other write block numbers sent by
the controller or by a command request from a node on the Modbus network or
operator control through the module’s Configuration/Debug port.

Write Block

These blocks of data transfer information from the ControlLogix processor to the
module. The following table describes the structure of the output image.

Write Block from Processor to Module

Word Offset

Description

Length

0

Write Block ID: -1 to 50

1

1 to 200

Write Data

200

201 to 247

Spare

47

The Write Block ID is an index value used to determine the location in the
module’s database where the data will be placed. Each transfer can move up to
200 words (block offsets 1 to 200) of data.