ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 150

Advertising
background image

Reference

MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 150 of 199

ProSoft Technology, Inc.

June 18, 2014

Register

Content

Description

10,064

Error Delay Counter

This parameter specifies the number of poll
attempts to be skipped before trying to re-establish
communications with a slave that has failed to
respond to a command within the time limit set by
the Response Timeout parameter. After the slave
fails to respond, the master will skip sending
commands that should have been sent to the slave
until the number of skipped commands matches
the value entered in this parameter. This creates a
sort of slow poll mode for slaves that are
experiencing communication problems.

10,065 to 10,069

Spare

6.5.4 Port 1 Commands

Register

Content

Description

10,070 to 10,077

Command #1

This set of registers contains the parameters for
the first command in the Master command list.
Refer to Master Command Configuration (page
37).

10,078 to 10,085

Command #2

Command #2 data set

-

-

-

12,662 to 12,669

Command #325

Command #325 data set

Note: To use up to 325 commands, your MVI56E-MCM module needs to have firmware version

3.01 or higher, and your MVI56E-MCM Add-On Instruction needs to be version 2.8 or higher.
Earlier versions support up to 100 commands.

6.5.5 Port 2 Commands

Register

Content

Description

12,670 to 12,677

Command #1

This set of registers contains the parameters for
the first command in the Master command list.
Refer to Master Command Configuration (page
37).

12,678 to 12,685

Command #2

Command #2 data set

-

-

-

15,626 to 15,629

Command #325

Command #325 data set

6.5.6 Misc. Status

Register

Content

Description

15,270

Program Scan Count

This value is incremented each time a complete
program cycle occurs in the module.

15,271 to 15,272

Product Code

These two registers contain the product code of
"MCM".