ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 49

Advertising
background image

MVI56E-MCM ♦ ControlLogix Platform

Configuration as a Modbus Master

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 49 of 199

June 18, 2014

The following COP

statement will copy the data from MCM.DATA.R

EAD

D

ATA

[0]

TO

[13]

into the array MCM_F

LOAT

_D

ATA

[0]

TO

[6].

The "Length" parameter is set to the number of Floating-Point values that must
be copied from the MCM.DATA.R

EAD

D

ATA

array.

2.4.3 Write Floats to Slave Device

To issue a Write command to Floating-Point addresses, use the configuration in
the following table. The table describes the Modbus Map for the Slave device.

Value

Description

Type

40261

KW

Demand (power)

Float. upper 16 bits

40263

VAR

Reactive Power

Float. upper 16 bits

40265

VA

Apparent Power

Float. upper 16 bits

40267

Power Factor

Float. upper 16 bits

40269

VOLTS

Voltage, line to line

Float. upper 16 bits

40271

VOLTS

Voltage, line to neutral

Float. upper 16 bits

40273

AMPS

Current

Float. upper 16 bits

You must use a COP

statement to copy the data from floating-point data tags

within the ControlLogix processor, into the MCM.DATA.W

RITE

D

ATA

array used

by the MVI56E-MCM module. Below is an example.

The length of this COP statement must now be 14. This will COP as many of the
MCM_F

LOAT

_D

ATA

values required to occupy the MCM.D

ATA

.W

RITE

D

ATA

array

for a length of 14. This will take 7 registers, MCM_F

LOAT

_D

ATA

[0]

TO

[6],

and

place that data into MCM.DATA.W

RITE

D

ATA

[0]

TO

[13].

You must configure the command to write all 7 floats (14 Modbus addresses) as
follows.