ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 37

Advertising
background image

MVI56E-MCM ♦ ControlLogix Platform

Configuration as a Modbus Master

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 37 of 199

June 18, 2014

Parameter

Description

Error Delay Counter

This parameter specifies the number of poll attempts to be skipped
before trying to re-establish communications with a slave that has
failed to respond to a command within the time limit set by the
Response Timeout parameter. After the slave fails to respond, the
master will skip sending commands that should have been sent to the
slave until the number of skipped commands matches the value
entered in this parameter. This creates a sort of slow poll mode for
slaves that are experiencing communication problems.

RespTO

0 to 65535 milliseconds response timeout for command before it will
either reissue the command, if R

ETRY

C

OUNT

>

0.

If the RetryCount =0 or if the designated number of retries have been
accomplished, then the Master will move on to the next command in
the list.

RetryCount

Number of times to retry a failed command request before moving to
the next command on the list.

Note: To use up to 325 commands, your MVI56E-MCM module needs to have firmware version

3.01 or higher, and your MVI56E-MCM Add-On Instruction needs to be version 2.8 or higher.
Earlier versions support up to 100 commands.

2.2.2 Master Command Configuration

This topic describes the communications with the Master Port and the Slave
devices that are connected to that port.

Verify you are in M

ONITOR

T

AGS

mode. Then use the scroll bar at the bottom of

the window to view a description of each parameter.