Chapter 1 Overview of the TimeProvider

Alarms

Alarms

The TimeProvider uses alarms to notify you when certain conditions are deteriorating
below user-specified levels. These alarms are indicated by shelf and card status
lamps (LEDs) and by TL1 messages reported over the serial/EIA-232 or LAN
communication ports. In addition, the input panel has a connector that provides
contact closures to activate external alarms.

You can provision the alarm level for most alarms to one of the following levels:
non-reportable (NR), non-alarm event (NA), minor (MN), major (MJ), or critical (CR).
Alarms related to the inputs are special cases; you can only provision input alarms
for minor, major, or critical. To help prevent spurious or transient input alarms, a
delay timer (FLTDELAY) allows you to provision a waiting period that starts after the
alarm condition occurs; the alarm is set at the end of the period. A similar timer
(CLRDELAY) clears the alarm after the alarm condition is no longer present.

For more information on connecting alarms, see

Making Alarm Connections

, on

page 70. For information on provisioning alarm levels, see

Provisioning the Alarm

Levels

, on page 126.

Synchronization Status Messages (SSMs)

The TimeProvider supports input and output SSMs. SSMs provide a method for
providing clock quality information to any equipment that uses synchronization
inputs.

Table 1-4

describes the ANSI SSM values and the traceability associated

with each value.

Table 1-5

describes the ITU SSM values and the traceability

associated with each value.

Recommendation: To prevent Non-Service Affecting LOS
alarms, Symmetricom recommends that you provision unused
inputs to the Disabled state.

Table 1-4. ANSI SSM Quality Level Definitions

Description

Quality Level

Abbreviation

Stratum 1 Traceable

1

PRS

Synchronized – traceability unknown

2

STU | UNK

Stratum 2 traceable

3

ST2 | TYPE II

Transit Node traceable

4

TNC | TYPE V

Stratum 3E traceable

5

ST3E | TYPE III

Stratum 3 traceable

6

ST3 | TYPE IV