Setting ethernet parameters, Setting, Ethernet parameters – Symmetricom EDGE CLOCK 1000 User Manual

Page 93

Advertising
background image

097-58001-02 Revision G – April 2008

TimeProvider User’s Guide

93

Chapter 4 Provisioning the TimeProvider

Setting Communications Parameters

Setting Ethernet Parameters

Before you can begin using the Ethernet port, you must provision the addresses
using the local Craft or Remote serial port.

If you are not planning to use the Ethernet port, you do not have to provision the
parameters in this section.

Setting the IP Addresses
Use the ED-EQPT command to provision the following IP addresses for the
TimeProvider:

IP Gateway address

IP address

IP subnet Mask

ED-EQPT:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;

This command has a default access level of ADMIN.

Sample Command

ED-EQPT::COMI:TS1000::IPGATE=127.0.0.1;

This command sets the IP Gate address to 127.0.0.1. Use an appropriate gateway
address for your network, and record the address in

Table 4-4

.

Autonomous Message

TP-SSU 03-10-24 10:15:04

A 1169 REPT EVT

“COMI:NA,IPGATE,NSA,03-10-24 10-15-04:\”IP GATEWAY

ADDRESS HAS CHANGED\””

;

Note: To avoid unexpected interruptions in NTP service, you must
restart the IMC card after you change either the Subnet Mask or the
IP Address when NTP is active.

<aid>

<keyword>

<value>

Description

Default

COMI

IPGATE

1.0.0.1
254.255.255.254

IP address of the default gateway

127.0.0.1

IPADDR

1.0.0.1
254.255.255.254

IP address of the Network
Element

127.0.0.1

IPSUBNET

1.0.0.1
255.255.255.254

Subnet mask IP address

255.255.
255.0