Procedure for single inverter systems, Connect positive cables, Connect a negative cables – Xantrex Technology SW Plus 4024 User Manual

Page 104: Procedure for single inverter systems –22

Advertising
background image

Installation

3–22

976-0043-01-02

Procedure for Single Inverter Systems

Before starting this procedure, please review

Figure 3-10, “DC Terminal

Connections on the Inverter” on page 3–20

and

Figure 3-11, “Battery

Cable Connection” on page 3–21

for the locations of the terminals and

details on attaching positive (+) and negative (–) cables to terminals on
the inverter DC end. Ensure the unit is properly grounded before
proceeding.

While performing the following procedure, please refer to

Figure 3-13,

“DC Connections to a Single Inverter” on page 3–23

.

Use the following procedure to connect the battery (or battery bank)
to the inverter.

1.

Connect POSITIVE cables:

a) Connect one cable from the battery POSITIVE terminal to a

circuit breaker in the DC disconnect (torque to manufacturer’s
recommendations). The DC disconnect should be located as close
to the batteries as possible.

b) Connect another cable from the other side of the same circuit

breaker to the inverter’s POSITIVE (+) terminal.

2.

Connect a NEGATIVE cables:

a) Connect one cable from the battery NEGATIVE terminal (torque

to manufacturer’s recommendations) to the ground bond in the
DC disconnect.

b) Connect another cable from the ground bond to the inverter’s

NEGATIVE (–) terminal.

3.

Ensure the correct polarity of the cables with a DC voltmeter (DVM).

4.

Use an insulated 1/2-inch wrench or socket to tighten the 5/16 SAE
nuts to 10-15 foot/lb for each inverter input terminal.

5.

Apply antioxidant paste to the battery terminals, if desired.

6.

Install the battery terminal covers (if used)—red for positive, black
for negative—over the inverter DC terminals and secure with the
screws and washers provided.