26 Gen Auto Run Setup Menu

Menu Heading 26 Gen Auto Run Setup Menu provides the menu items
for setting the parameters for starting the generator based on AC current
and/or battery voltage.

26A Load Start Amps AC

This menu items sets the AC load current that initiates automatic
generator start. When the current remains above this setting continuously
for time set in 26B Load Start Delay Min, the generator starts.

26B Load Start Delay Min

This menu items sets the time delay period that initiates automatic
generator starting. When the current remains above the 26A Load Start
Amps AC
setting continuously for this period, the generator starts.

26C Load Stop Delay Min

This menu item sets the amount of time the generator continues to run
after the load current (determined by the 04E Load Amps AC meter)
decreases below the 26A Load Start Amps AC setting.

26D 24 Hr Start Volts DC

This menu item sets the battery’s DC voltage level which initiates
automatic generator starting whenever the voltage drops below this
setting continuously for 24 hours. This item is not temperature
compensated and is defeated during the quiet time period set in the
24 Generator Timers Menu.

26E 2 Hr Start Volts DC

This menu item sets the battery’s DC voltage level which initiates
automatic generator starting whenever the voltage drops below this
setting continuously for 2 hours. This item is not temperature
compensated and is defeated during the quiet time period set in the
24 Generator Timers Menu.

26 Gen Auto Run
Setup Menu

26A Load Start
Amps AC

26B Load Start
Delay Min

26C Load Stop
Delay Min

26D 24 Hr Start
Volts DC

26E 2 Hr Start
Volts DC