Procedure for dual-inverter systems, Connect positive cables, Connect negative cables – Xantrex Technology SW Plus 4024 User Manual

Page 106: Procedure for dual-inverter systems –24

Advertising
background image

Installation

3–24

976-0043-01-02

Procedure for Dual-Inverter Systems

Before starting this procedure, please review

Figure 3-10, “DC Terminal

Connections on the Inverter” on page 3–20

and

Figure 3-11, “Battery

Cable Connection” on page 3–21

for the locations of the terminals and

details on attaching positive (+) and negative (–) cables to terminals on
the inverter DC end. Ensure the unit is properly grounded before
proceeding.

While performing the following procedure, please refer to

Figure 3-14

.

Use the following procedure to connect the battery (or battery bank)
to the inverters.

1.

Connect POSITIVE cables:

a) one cable from the battery POSITIVE terminal to a circuit

breaker in the DC disconnect (torque to manufacturer’s recom-
mendations). The DC disconnect should be located as close to the
batteries as possible.

b) a second cable from the same battery POSITIVE terminal to

another circuit breaker in the DC disconnect.

c) a third cable from the first circuit breaker in the DC disconnect to

the L1 inverter POSITIVE (+) terminal.

d) a fourth cable from the second DC disconnect to the L2 inverter

POSITIVE (+) terminal.

2.

Connect NEGATIVE cables:

a) one cable from the same battery NEGATIVE terminal (torque to

manufacturer’s recommendations) to the ground bond in the DC
disconnect.

b) a second cable from the same battery NEGATIVE terminal

(torque to manufacturer’s recommendations) to the ground bond
in the DC disconnect.

c) a third one from the ground bond in the DC disconnect to the L1

inverter NEGATIVE (–) terminal.

d) a fourth one from the ground bond in the DC disconnect to the

L2 inverter NEGATIVE (–) terminal.

3.

Ensure the correct polarity of the cables with a DC voltmeter (DVM).

4.

Use an insulated 1/2 inch wrench or socket to tighten the 5/16 SAE
nuts to 10-15 foot/lb for each inverter input terminal.

5.

Apply antioxidant paste to the battery terminals, if desired.

6.

Install the battery terminal covers (if used)—red for positive, black
for negative—over the inverter DC terminals and secure with the
screws and washers provided.