Time-of-use (tou) metering, Figure 2-23 time-of-use metering, Time-of-use (tou) metering –45 – Xantrex Technology SW Plus 4024 User Manual

Page 79: Figure 2-23, Time-of-use metering –45

Advertising
background image

On-Grid Applications

976-0043-01-02

2–45

Time-of-Use (TOU) Metering

Utilities use TOU metering to determine utility charges during peak usage
hours and to impose a surcharge. The inverter can be configured to
overcome these peak charges by using a battery (or battery bank) to store
energy during the inexpensive energy hours and consumes the battery
energy during expensive energy hours.

When in this mode, the inverter is programmed to only use utility power
during user-specified times during the day. This helps the consumer take
advantage of lower utility rates by using power from the battery bank
during times that utility power is most expensive.

See

“21 Grid (AC1) Usage Menu” on page 7–16

for instructions for

setting these parameters.

Energy management determines when utility power is used. Start and
Stop times are programmed into Menu Items 21B and 21C depending on
when you want the inverter to use utility power.

In the example below,

Figure 2-23

shows the inverter disconnects from

the utility grid at 6:00 PM and supports the connected load from batteries.
It continues to run until 9:00 PM. It then reconnects to the utility grid,
passing AC through to the connected load, and begins maintaining the
batteries based on the battery charger settings in the Basic Setup Menu
(Float or Silent).

Figure 2-23 Time-of-Use Metering

00

6

1

2

3

4

5

7

8

9

10

11

12

23

22

17

16

15

14

13

GRID USAGE END

TIME 18:00 (6 PM)

OPERATING FROM

UTILITY GRID AND

BATTERY CHARGING

OPERATING

FROM INVERTER

DURING PEAK

UTILITY PERIOD

18

21

20

19

GRID USAGE BEGIN

TIME 21:00 (9 PM)

Advertising
This manual is related to the following products: