Figure 7-8 RY7 and RY8 Timing Diagram

The generator auto-stop sequence is initiated if:

1) The time set in 24C QUIET TIME BEGIN has been reached or passed. This setting will disable 2, 3, and 4 start-scenarios below.

2) If the battery voltage has been held at the 12B BULK VOLTS DC setting for the time set in 12H MAX BULK/EQ TIMER H:M or if
the voltage has reached the 12F BULK DONE AMPS AC setting.

3) If the load amps remains below the 26A LOAD START AMPS AC setting and remains longer than the period set in 26C LOAD
STOP DELAY MINUTES.

4) If the time set for the generator to stop in 24B GEN RUN TIME STOP H:M is reached.

5) If the time set in 24H RN2/MAX GEN RUN H:M is reached and 25A RY7 MODE is set to RN2.

The generator manual-stop sequence is initiated if OFF is selected in 02A GENERATOR (OFF AUTO ON).

The next generator auto-start sequence is initiated.
(RN1 and GS modes will make six attempts to start the generator.
RN2 will only make one attempt to start the generator.)

The Generator auto-start sequence is initiated if:

1) The time set in 24D QUIET TIME END has been reached or passed.

2) If the battery voltage remains below the 11C LOW BATTERY CUT OUT VDC setting for the required period of time or if below the READ
LBCO 30 SEC START VDC setting for 30 seconds.

3) If the load amps reaches the 26A LOAD START AMPS AC setting and remains longer than the period set in 26B LOAD START DELAY
MINUTES.

4) If the time set for the generator to run in 24A GEN RUN TIME START H:M is reached.

The manual generator start sequence is initiated if generator is manually turned on via SET GENERATOR to ON.

The generator will stop immediately (no cooldown period) if an inverter fault is
detected or if OFF is selected in 02A GENERATOR (OFF AUTO ON).

Time (Sec)

RY8

Relays on GEN START MODULE (GSM)

OFF = relay contact closed from N.C. to COM (relay de-energized)
ON = relay contact closed from N.O. to COM (relay energized)

0

8

18

28

88

100

+100

+220

0

8

18

OFF

ON

ON

OFF

OFF

ON

ENERGIZED

(COM to N.O. connected)

OFF

OFF

ENERGIZED

(COM to N.O. connected)

START
DELAY

PERIOD

8 seconds

FIXED

SET PRE

CRANK

SECONDS

10 seconds

default

SET MAX

CRANK

SECONDS

10

seconds

default

(RY8 goes

off with a
1 second

delay when

AC HOT IN

exceeds

80 Vac

Set Gen

WARM-UP SECONDS

60 seconds

default

(Starts once voltage

exceeds

80 Vac)

Lock on

Good
Delay

period

12

seconds

fixed

(Starts

when AC

is within

110 to 130

Vac

(default)

and

53 to 67

Hz)

GEN RUN PERIOD

(Determined by

generator auto-run

configuration settings

COOL

DOWN

PERIOD

2 minutes

default

(Only used

if AUTO is

selected in

02A

Generator

(OFF AUTO

ON)

Generator

is OFF

and

waiting for

next auto-

generator

start

sequence)

START
DELAY

PERIOD

8 seconds

fixed

SET PRE

CRANK

SECONDS

10 seconds

default

OFF

(COM to N.C. connected)

DE-ENERGIZED

ON

OFF

ON

DE-ENERGIZED

(COM to N.C. connected)

RY7

RN1

GS

RN2