Figure 7-5 generator control mode (rn2), 25a ry7 mode, 25a ry7 mode –30 – Xantrex Technology SW Plus 4024 User Manual

Page 208: Figure 7-5, Generator control mode (rn2) –30

Advertising
background image

Advanced Setup

7–30

976-0043-01-02

Guidelines for setting this menu item:

When using a DC generator as a charging source, none of the
inverter's charge control features (bulk, absorption, float) will be
available. For battery protection, insure that external charge
management equipment is installed between the charger and the
batteries.

25A RY7 Mode

This menu item allows relay 7 (RY7) to provide three different relay
functions to accommodate either AC or DC generators.

The settings available for AC generators are GS and RN1. These
selections are monitored from the AC2 (generator) input, which tell the
inverter the generator is running.

The setting available for DC generators (or AC generators which do not
require monitoring) is RN2. Since there is no monitoring of the generator
by the inverter in this mode, only one attempt is made to start the
generator.

GS

This selection (GlowStop) provides a momentary contact closure

between contacts N.O. (Normally Open) and COM.

When GS is selected as the function of the RY7 relay, the RY7 COM and
RY7 N.O. contacts remain open while the generator is running. The
contacts close when it is time for the generator to be stopped, then they
reopen. This is useful for generators that require a stop signal to shut
down the generator.

The glowstop setting can also be used for a diesel generator. This relay
can be used to provide both the glow and stop signals. RY7 is signaled to
close (between RY7’s COM and N.O. contacts) before cranking (Glow
Plug warming) and when stopping.

Figure 7-5 Generator Control Mode (RN2)

AC

LOADS

INVERTER/

CHARGER

DC

AC

GEN START

MODULE

CONTROL

BATTERY

CONTROL

DC

GENERATOR

DC

25A RY Mode
GS RN1 RN2