Battery Information

C–12

976-0043-01-02

Connect to inverter

To connect to the inverter:

1.

Connect a cable from the positive terminal of the first battery string to
the inverter’s positive DC terminal (via a fused device).

2.

Connect the negative terminal of the last battery string to the negative
terminal of inverter’s DC terminal.

Battery Connections for Stacked Inverters

When using inverters in a stacked configuration, the same battery bank
must be used for both inverters. To ensure even charging of the batteries,
each inverter must be connected to both strings (i.e., positive cable to
string two, and negative cable to string one for inverter 1, and positive
cable to string one and negative cable to string two for inverter 2) as
shown in the diagram below.

Figure C-6 “Series-Parallel” Configuration Wired to the Inverter

+

12 V

12 V

+

+

12 V

12 V

+

12 V

12 V

12 V

12 V

+

48 V INVERTER

(Total battery capacity = 200 Ah)

+

+

+

+

Connection from Series String 2 to

inverter's negative (–) terminal

Series String 2

Series String 1

Connection from Series String 1
to inverter's positive (+) terminal

Each battery's amp-hour

rating is 100 Ah.

SHUNT

DC Disconnect (can be

either a circuit breaker or a

fuse with a disconnect)

6

6

6

6

6

6

6

6

24

700

350

Figure C-7 Example of Battery Connections for Stacked Inverters
(24 Vdc shown)

DC CONDUIT

FOR

INVERTER 1

+

12 Volt

Battery

200 Ah

+

12 Volt
Battery
200 Ah

+

12 Volt
Battery
200 Ah

Series String 1

Series String 2

DC CONDUIT

FOR

INVERTER 2

24 VDC/200 Ah

24 VDC/200 Ah

+

12 Volt

Battery

200 Ah

Shunt

Batteries in

Parallel

24 VDC 400 Ah