Table b-4 – Xantrex Technology SW Plus 4024 User Manual

Page 282

Advertising
background image

Configuration Settings

B–8

976-0043-01-02

Table B-4 Basic Setup Default and User Settings for the Sine Wave Plus 5548 Model

Sine Wave Plus

5548

User Settings

Basic Setup Menus

Range/Display

Default

10 Time of Day Setup Menu

See

“10 Time of Day Setup Menu” on page 6–11

for details.

10A Set Hour

00:00:00 to
23:50:00

00:00:00

10B Set Minute

00:00:00 to
00:09:00

00:00:00

10C Set Second

00 to 59

00:00:00

11 Inverter Setup Menu

See

“11 Inverter Setup Menu” on page 6–12

for details.

11A High Battery Cut Out Vdc

32.2 to 68.0

64.0

11B Low Battery Cut In Vdc

32.2 to 67.8

52.0

11C Low Battery Cut Out Vdc

32.0 to 67.8

44.0

11D LBCO Delay Minutes

01 to 255

15

11E Search Watts (SRCH)

00 to 248

08

12 Battery Charging Menu

See

“12 Battery Charging Menu” on page 6–19

for details.

12A Finish Stage

SILENT FLOAT

FLOAT

12B Bulk Volts DC

40.0 to 64.0

57.6

12C Float Volts DC

40.0 to 64.0

53.6

12D Equalize Volts DC

40.0 to 64.0

57.6

12E Max Charge Amps AC

01 to 45

40

12F Bulk Done Amps AC

00 to 20

10

12G EQ Vdc Done Timer

00:00 to 23:50

02:00

12H Max Bulk/EQ Timer

00:00 to 23:50

05:00

12I Temp Comp

LeadAcid NiCad

LeadAcid

13 AC Inputs Menu

See

“13 AC Inputs Menu” on page 6–26

for details.

13A Grid (AC1) Amps AC

00 to 60

60

13B Gen (AC2) Amps AC

00 to 60

30

13C Input Upper Limit Vac

125 to 150

130

13D Input Lower Limit Vac

80 to 115

110

14 Save/Restore Settings Menu

See

“14 Save/Restore Settings Menu” on page 6–29

for details.