Xantrex Technology SW Plus 4024 User Manual

Page 151

Advertising
background image

Basic Setup Summary

976-0043-01-02

6–3

11C Low Battery Cut Out Vdc

11.0 to 33.9

22.0

32.0 to 67.8

44.0

page 6–13

11D LBCO Delay Minutes

01 to 255

15

01 to 255

15

page 6–13

11E Search Watts (SRCH)

00 to 248

08

00 to 248

08

page 6–14

End Menu 11

12 Battery Charging Menu

See

“12 Battery Charging Menu” on page 6–19

for details.

12A Finish Stage

SILENT
FLOAT

FLOAT

SILENT
FLOAT

FLOAT

page 6–19

12B Bulk Volts DC

20.0 to 32.0

28.8

40.0 to 64.0

57.6

page 6–20

12C Float Volts DC

20.0 to 32.0

26.8

40.0 to 64.0

53.6

page 6–20

12D Equalize Volts DC

20.0 to 32.0

28.8

40.0 to 64.0

57.6

page 6–20

12E Max Charge Amps AC

01 to 20

20

01 to 20

20

page 6–22

12F Bulk Done Amps AC

00 to 20

10

00 to 20

10

page 6–23

12G EQ Vdc Done Timer

00:00 to 23:50 02:00

00:00 to
23:50

02:00

page 6–24

12H Max Bulk/EQ Timer

00:00 to 23:50 05:00

00:00 to
23:50

05:00

page 6–25

12I Temp Comp

LeadAcid
NiCad

LeadAcid

LeadAcid
NiCad

LeadAcid

page 6–25

End Menu 12

13 AC Inputs Menu

See

“13 AC Inputs Menu” on page 6–26

for details.

13A Grid (AC1) Amps AC

00 to 60

60

00 to 60

60

page 6–27

13B Gen (AC2) Amps AC

00 to 60

30

00 to 60

30

page 6–27

13C Input Upper Limit Vac

125 to 150

130

125 to 150

130

page 6–28

13D Input Lower Limit Vac

80 to 115

110

80 to 115

110

page 6–28

End Menu 13

14 Save/Restore Settings Menu

See

“14 Save/Restore Settings Menu” on page 6–29

for details.

14A Push INV now to save
settings

Push INV now to save settings

page 6–29

14B Push GEN to restore settings

Push GEN to restore settings

page 6–29

Table 6-1 Basic Setup Menu Default Settings for the Sine Wave Plus 2524 and 2548 Models

Basic Setup Menus

Sine Wave Plus

2524

Sine Wave Plus

2548

See Page

Range/
Display

Default

Range/
Display

Default

Advertising
This manual is related to the following products: