Install Utility Wiring to the Inverter Input (On-Grid Applications only)

The following instructions are illustrated in

Figure 3-21, “Utility Wiring

to the Inverter Input” on page 3–39

.

Install the wiring from the inverter to the utility panel as follows:

1.

Feed the HOT, NEUTRAL, and GROUND input wires (via conduit)
from the inverter to the utility panel. Leave three to six inches of extra
wire at each end.

2.

Connect a GROUND (green or bare) wire:

a) from the inverter AC GROUND bar, and

b) to the utility panel GROUND bar.

3.

Connect a NEUTRAL (white) wire:

a) from the inverter NEUTRAL 1 terminal, and

b) to the utility panel NEUTRAL bus.

4.

Connect a HOT (black) wire:

a) from the inverter AC1 GRID terminal, and

b) to the appropriate utility panel circuit breaker.

5.

Torque all inverter terminal block connections to 25 inch-pounds.

CAUTION: Damage to Equipment

The inverter’s AC output must never be wired to any AC source voltage such as a
generator output or utility panel. This will cause severe damage to the inverter
which is not covered under warranty.

Important:

Make the connections to the inverter first. Wiring to the inverter’s

main breaker in the utility panel is performed after all connections have been
made in the inverter.