04 meters menu, Note, 04a battery actual vdc – Xantrex Technology SW Plus 4024 User Manual

Page 240: 04 meters menu –22, 04a battery actual vdc –22

Advertising
background image

Operation

8–22

976-0043-01-02

04 Meters Menu

The Meters Menu provides information about system performance. The
menus under this heading are read-only. This information includes the
following menu items to assist the user in monitoring system
performance:

04A Battery Actual Volts DC

04B Battery Compensated Volts DC

04C Inverter/Charger Amps AC

04D Input Amps AC

04E Load Amps AC

04F Inverter Volts AC

04G Grid (AC1) Volts AC

04H Generator (AC2) Volts AC

04I Frequency Hertz

04J Maximum Bulk/EQ Time

04K Battery Temp Degrees C

04L Fan Speed

04A Battery Actual Vdc

This menu item displays the actual DC battery voltage. This value is used
for setting the following menu items.

11C Low Battery Cut Out Vdc

11A High Battery Cut Out Vdc

22B Low Battery Xfer Vdc

11B Low Battery Cut In Vdc

22A High Battery Xfer Vdc

04 Meters Menu

Note:

The AC ammeters have an approximate 1-amp tolerance. Additionally,

the meters provided in menus 04C, 04D and 04E measure the real, in-phase AC
component of the current. This is the portion of the power that is actually drawn
from the batteries, allowing better estimation of the DC power consumed by the
load or the battery charger. Measurements taken with conventional AC DVMs
usually read apparent current and may differ from these readings.

04A Battery