Table 6-4, Table 6-5 – Xantrex Technology SW Plus 4024 User Manual

Page 169

Advertising
background image

Menu Item Descriptions

976-0043-01-02

6–21

The following settings (

Table 6-5

) are guidelines only. Refer to your

battery vendor for specific settings and battery maintenance guidelines.

Table 6-4 Battery Voltages For Setting Charging Parameters

Battery Type

BULK VOLTS

FLOAT VOLTS

Equalization Charge
Process

Set
Temp
Comp

24-volt
models

48-volt
models

24-volt
models

48-volt
models

Sealed Gel
Lead Acid

28.2 Vdc

56.4 Vdc

27.2 Vdc

54.4 Vdc

Not recommended -
consult manufacturer

LeadAcid

AGM
Lead Acid

28.8 Vdc

57.6 Vdc

26.8 Vdc

53.6 Vdc

Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations

LeadAcid

Maintenance-Free
RV/Marine
Lead Calcium
Battery

28.8 Vdc

57.6 Vdc

26.8 Vdc

53.6 Vdc

Not recommended -
consult manufacturer

LeadAcid

Deep-cycle,
Liquid Electrolyte
Lead Antimony
Battery

29.2 Vdc

58.4 Vdc

26.8 Vdc

53.6 Vdc

Charge to 31.0 Vdc
(24-volt models) or 62
Vdc (48-volt models) or
as per manufacturer
recommendations

LeadAcid

NiCad or NiFe
Alkaline Battery
(using 10 cells in
series)

32.0 Vdc

64.0 Vdc

29.0 Vdc

58.0 Vdc

Consult Manufacturer

NiCad

Table 6-5 Battery Charging Current and Timer Default Settings

Menu Item

SW Plus
2524
Default
Settings

SW Plus
2548
Default
Setting

SW Plus
4024
Default
Settings

SW Plus
4048
Default
Setting

SW Plus
5548
Default
Setting

12E Max Charge Amps

20 amps

20 amps

30 amps

30 amps

40 amps

12F Bulk Done Amps AC

10 amps

10 amps

10 amps

10 amps

10 amps

12G EQ Vdc Done Timer h:m 02:00

02:00

02:00

02:00

02:00

12H Max Bulk/EQ Timer h:m 05:00

05:00

05:00

05:00

05:00

12I Temp Comp

LeadAcid

LeadAcid

LeadAcid

LeadAcid

LeadAcid