Xantrex Technology SW Plus 4024 User Manual

Page 261

Advertising
background image

Electrical Specifications

976-0043-01-02

A–3

Electrical Specifications

Sine Wave Plus

4024

Sine Wave Plus

4048

Sine Wave Plus

5548

AC Input Voltage (nominal)

120 Vac

120 Vac

120 Vac

AC Input Voltage Range

80 to 150 Vac

80 to 150 Vac

80 to150 Vac

AC Input Current

60 amps AC Pass-
through/ 30 amps
AC Charging

60 amps AC Pass-
through/ 30 amps
AC Charging

60 amps AC Pass-
through/ 45 amps
AC Charging

AC1 Input Frequency Range

55 to 65 Hz

55 to 65 Hz

55 to 65 Hz

AC2 Input Frequency Range

54 to 67 Hz

54 to 67 Hz

54 to 67 Hz

Continuous Power (@ 25°C)

4000 VA

4000 VA

5500 VA

Efficiency (Peak) in inverter mode

94%

95%

95%

Inverter Voltage (RMS)

120 Vac

120 Vac

120 Vac

Inverter Voltage Regulation

± 3%

± 3%

± 3%

Frequency (Nominal ±0.04%
Crystal Controlled - Invert Mode)

60 Hz

60 Hz

60 Hz

Continuous Output (@25° C)

33 amps rms

33 amps rms

46 amps rms

Surge Capability (@25° C)

5 second rating (resistive) 85 amps rms

95 amps rms

105 amps rms

Over current trip point 125 amps Peak

175 amps Peak

175 amps Peak

Inverter Voltage THD
(Total Harmonic Distortion)
(Resistive Load)

< 5%

< 5%

< 5%

Automatic Transfer Relay

60 amps

60 amps

60 amps

DC Input Voltage (Nominal)

25.2 Vdc

50.4 Vdc

50.4 Vdc

DC Input Voltage Range

22 to 32 Vdc

44 to 64 Vdc

44 to 64 Vdc

DC Current at Rated Power (Invert
Mode, Internal temp. stabilized)

190 amps DC

95 amps DC

135 amps DC

Idle Consumption (Invert Mode/No
Load)

< 16 watts

< 20 watts

< 20 watts

Search Mode Consumption
(Default setting)

< 2 watts

< 2 watts

< 2 watts

Continuous Charge Rate
(at 120 Vac input)

110 amps DC

60 amps DC

75 amps DC

Advertising