20D Must Float Time Min

This menu item sets the minimum amount of time after the 20A Refloat
High Volts DC
and 20B Refloat Low Volts DC settings have been
reached that the inverter will maintain the float voltage level on the
batteries before it reaches the 20C Float Done Amps AC setting and
returns to the Silent mode.

21 Grid (AC1) Usage Menu

This menu sets the conditions that determine how and when the inverter’s
AC1 (grid) input will be used.

To program grid usage parameters, the Advanced Setup Menu Headings
21 Grid (AC1) Usage Menu and 22 Battery Xfer Menu are used.

Table 7-4 Calculating the Float Done Amps for a 24-volt,
700 amp-hour Battery

Step

Instruction

Equation

1

Multiply the total battery amp
hours by 1%

700 x 1% = 7
(DC Max Charge Rate)

2

Divide the DC Max Charge Rate
by 4

7 ÷ 4 = 1

3

Set the 20C Float Done Amps
AC
parameter.

1 amps AC

Table 7-5 Calculating the Float Done Amps for a 48-volt,
350 amp-hour Battery

Step

Instruction

Equation

1

Multiply the total battery amp
hours by 1%

350 x 1% = 3.5
(DC Max Charge Rate)

2

Divide the DC Max Charge Rate
by 2

3.5 ÷ 2 = 1

3

Set the 20C Float Done Amps
AC
parameter.

1 amps AC

20D Must Float
Time Min

21 Grid AC1 Usage
Menu