Advanced Setup Summary

976-0043-01-02

7–5

Table 7-2 Advanced Setup Default Settings for the

Sine Wave Plus

4024 and 4048 Models

Advanced Setup Menus

Sine Wave Plus

4024

Sine Wave Plus

4048

See Page

Range/Display

Default
Settings

Range/Display

Default
Settings

20 Silent Setup Menu

See

“20 Silent Setup Menu” on page 7–13

for details.

20A Refloat High Volts DC

16.1 to 33.9

28.4

32.2 to 67.8

56.8

page 7–15

20B Refloat Low Volts DC

16.1 to 33.8

25.0

32.2 to 67.8

50.0

page 7–15

20C Float Done Amps AC

00 to 40

10

00 to 40

10

page 7–15

20D Must Float Time Min

00 to 255

05

00 to 255

05

page 7–15

End Menu 20

21 Grid AC1 Usage Menu

See

“21 Grid (AC1) Usage Menu” on page 7–16

for details.

21A Grid Usage

SB BX

SB

SB BX

SB

page 7–17

21B Grid Usage Begin h:m

00:00 to 23:50

21:00

00:00 to 23:50

21:00

page 7–17

21C Grid Usage End h:m

00:00 to 23:50

21:00

00:00 to 23:50

21:00

page 7–18

End Menu 21

22 Battery Xfer (BX) Menu

See

“22 Battery Xfer (BX) Menu” on page 7–18

for details.

22A High Xfer (HBX) Vdc

16.1 to 33.9

27.0

32.2 to 67.8

54.0

page 7–19

22B Low Xfer (LBX) Vdc

16.1 to 33.8

23.0

32.2 to 67.8

46.0

page 7–19

End Menu 22

23 ALM Relays Menu

See

“23 ALM Relays Menu” on page 7–19

for details.

23A RY9 VDC Energized

22.1 to 35.5

26.0

44.2 to 71.0

52.0

page 7–20

23B RY9 VDC DeEnergized

20.0 to 35.5

22.0

40.0 to 71.0

44.0

page 7–20

23C RY9 Delay at DeEngz.
Min

00 to 255

10

00 to 255

10

page 7–20

23D RY10 VDC Energized

10.0 to 32.0

28.8

20.0 to 64.0

57.6 Vdc

page 7–20

23E RY10 VDC DeEnergized 10.0 to 32.0

26.8

20.0 to 64.0

53.6 Vdc

page 7–21

23F RY10 Delay at DeEngz.
Min

00 to 255

10

00 to 255

10

page 7–21

23G RY11 Mode

Cooldown Error

Error

Cooldown Error Error

page 7–21

End Menu 23

24 Generator Timers Menu

See

“24 Generator Timers Menu” on page 7–26

for details.

24A Gen Run Time Start h:m 00:00 to 23:50

08:00

00:00 to 23:50

08:00

page 7–27