01D Bypass Mode

The Bypass Modecloses the internal bypass relays and allows the AC
connected to the selected input (AC1 or AC2) to pass directly through to
the loads without being monitored for AC voltage or frequency quality.

NORM

When NORM is selected in the menu, the available inputs are

monitored for voltage and frequency.

AC1, AC2

If AC1 or AC2 is selected in this menu, the AC applied to

that input will not be monitored for voltage or frequency problems which
will pass directly through to the load, bypassing the inverter’s monitoring
circuits.

02 Generator ON/OFF Menu

The 02 Generator ON/OFF Menu is used for controlling a generator
equipped with remote start features and connected to the inverter by way
of the optional GSM. The generator can be manually switched ON or
OFF using the inverter control module or set to run automatically based
on programmed usage parameters. This menu heading also provides
generator status menus (02B through 02F) to help determine “why” a
generator started.

01D Bypass Mode

AC1 NORM AC2

Important:

All system functions are disabled in this mode and can only be

restored by selecting NORM. After returning to NORM, you must reselect your
user settings in the 01A Inverter menu item.

CAUTION: Damage to AC Loads

When Bypass Mode is selected, the

Sine Wave Plus

allows any AC power

supplied (utility or generator) to pass through the inverter to AC loads. If the
source of AC is not adequately regulated it can cause instability in voltage and
frequency which can damage connected AC loads. Xantrex does not recommend
use of Bypass Mode in areas of unstable AC power supply.

02 Generator

ON/OFF Menu

Note:

Auto-starting or controlling a generator with the inverter is only

possible with generators that have an electric starter and are compatible with
two- or three-wire external relay control. The optional GSM accessory is
required to perform automatic-generator starting operations.