Dual inverters, To ground a dual-inverter configuration, Figure 3-8 dc grounding of dual inverters – Xantrex Technology SW Plus 4024 User Manual

Page 99: Figure 3-8, Dc grounding of dual inverters –17

Advertising
background image

DC Wiring

976-0043-01-02

3–17

Dual Inverters

To ground a dual-inverter configuration:

1.

Connect the ground bond in the DC disconnect between the inverters
and the batteries to the primary grounding electrode, in accordance
with local and national electrical codes.

2.

Connect the NEGATIVE (–) terminal of the battery bank to the
ground bond inside the DC disconnect.

3.

Connect an appropriately sized GROUND wire from the Chassis
Bonding Lug on the L1 inverter DC end to the ground bond inside the
DC disconnect.

4.

Connect a second appropriately sized GROUND wire from the
Chassis Bonding Lug on the L2 inverter DC end to a different
terminal in the ground bond inside the DC disconnect.

Figure 3-8 DC Grounding of Dual Inverters

Advertising