Advanced setup menu, Table b-5 – Xantrex Technology SW Plus 4024 User Manual
Page 284
Configuration Settings
B–10
976-0043-01-02
Advanced Setup Menu
provides a list of Advanced Setup Menu headings and menu
items, with available set points. This table also provides the default
settings for each menu item as programmed in the factory. The last
column “User Settings” is provided for you to write in the settings
specific to your installation.
Table B-5 Advanced Setup Default and User Settings for the Sine Wave Plus 2524 and
2548 Models
Advanced Setup Menus
Sine Wave Plus
2524
Sine Wave Plus
2548
User
Settings
Range/
Display
Default
Settings
Range/
Display
Default
Settings
20 Silent Setup Menu
“20 Silent Setup Menu” on page 7–13
for details.
20A Refloat High Volts DC
16.1 to 33.9
28.4
32.2 to 67.8
56.8
20B Refloat Low Volts DC
16.1 to 33.8
25.0
32.2 to 67.8
50.0
20C Float Done Amps AC
00 to 40
10
00 to 40
10
20D Must Float Time Min
00 to 255
05
00 to 255
05
21 Grid AC1 Usage Menu
“21 Grid (AC1) Usage Menu” on page 7–16
for details.
21A Grid Usage SB BX
SB BX
SB
SB BX
SB
21B Grid Usage Begin h:m
00:00 to
23:50
21:00
00:00 to
23:50
21:00
21C Grid Usage End h:m
00:00 to
23:50
21:00
00:00 to
23:50
21:00
22 Battery Xfer (BX) Menu
“22 Battery Xfer (BX) Menu” on page 7–18
for details.
22A High Xfer (HBX) Vdc
16.1 to 33.9
27.0
32.2 to 67.8
54.0
22B Low Xfer (LBX) Vdc
16.1 to 33.8
23.0
32.2 to 67.8
46.0
23 ALM Relays Menu
“23 ALM Relays Menu” on page 7–19
for details.
23A RY9 Vdc Energized
22.1 to 35.5
26.0
44.2 to 71.0
52.0
23B RY9 Vdc DeEnergized
20.0 to 35.5
22.0
40.0 to 71.0
44.0
23C RY9 Delay at DeEngz. Min
00 to 255
10
00 to 255
10
23D RY10 VDC Energized
10.0 to 32.0
28.8
20.0 to 64.0
57.6
23E RY10 VDC DeEnergized
10.0 to 32.0
26.8
20.0 to 64.0
53.6
23F RY10 Delay at DeEngz. Min
00 to 255
10
00 to 255
10
23G RY11 Mode
Cooldown
Error
Error
Cooldown
Error
Error