Advanced Setup

7–8

976-0043-01-02

23 ALM Relays Menu

See

“23 ALM Relays Menu” on page 7–19

for details.

23A RY9 VDC Energized

44.2 to 71.0

52.0

page 7–20

23B RY9 VDC DeEnergized

40.0 to 71.0

44.0

page 7–20

23C RY9 Delay at DeEngz. Min

00 to 255

10

page 7–20

23D RY10 VDC Energized

20.0 to 64.0

57.6 Vdc

page 7–20

23E RY10 VDC DeEnergized

20.0 to 64.0

53.6 Vdc

page 7–21

23F RY10 Delay at DeEngz. Min

00 to 255

10

page 7–21

23G RY11 Mode

Cooldown Error

Error

page 7–21

End Menu 23

24 Generator Timers Menu

See

“24 Generator Timers Menu” on page 7–26

for details.

24A Gen Run Time Start h:m

00:00 to 23:50

08:00

page 7–27

24B Gen Run Time Stop h:m

00:00 to 23:50

08:00

page 7–27

24C Quiet Time Begin h:m

00:00 to 23:50

08:00

page 7–27

24D Quiet Time End h:m

00:00 to 23:50

08:00

page 7–28

24E Gen Exercise Period Days

00 to 255

30

page 7–28

24F Gen Exercise Timer Min

00 to 255

15

page 7–28

24G Gen Cooldown Timer Min

00 to 255

02

page 7–28

24H RN2/Max Gen Run h:m

00:00 to 23:50

08:00

page 7–29

End Menu 24

25 Gen Starting Details Menu

See

“25 Gen Starting Details Menu” on page 7–29

for details.

25A RY7 Mode

GS RN1 RN2

GS

page 7–30

25B Gen Warm-up
Second/Minute

0 to 127
/0 to 127

10
Seconds

page 7–37

25C Pre Crank Seconds

00 to 255

10

page 7–37

25D Max Cranking Seconds

01 to 15

10

page 7–37

25E Post Crank Seconds

00 to 255

30

End Menu 25

26 Gen Auto Run Setup Menu

See

“26 Gen Auto Run Setup Menu” on page 7–38

for details.

Table 7-3 Advanced Setup Default Settings for the

Sine Wave Plus

Plus 5548 Models

Advanced Setup Menus

Sine Wave Plus

5548

See Page

Range/Display

Default