Inverter operation status (yellow), Figure 8-2 inverter operation status leds, Grid tie led – Xantrex Technology SW Plus 4024 User Manual

Page 222: Invert led, Search mode indication, Standby mode indication, Inverter operation status (yellow) –4, Figure 8-2, Inverter operation status leds –4

Advertising
background image

Operation

8–4

976-0043-01-02

Inverter Operation Status (Yellow)

There are two yellow LEDs to indicate the following inverter operational
modes.

GRID TIE LED - This feature is not available at this time.

INVERT LED

GRID TIE LED

The Grid Tie feature is not enabled on these models. Therefore, the GRID
TIE LED will not be illuminated during normal operation. It might,
however, flash during initial startup or during an LED test.

INVERT LED

The INVERT LED indicates the inverter is operational and inverter power
to the AC output is available to power the load if needed. Therefore, this
LED will be illuminated during normal operation.

Search Mode Indication

If the INVERT LED is blinking and no other

LEDs are illuminated, the inverter is in the energy saving SEARCH Mode
and monitoring the output for a load greater than the 01C and 11E Search
Watts
setting.

Standby Mode Indication

If the INVERT LED blinks and the AC1 or

AC2 LEDs are illuminated, the inverter is in Standby Mode and is ready
to engage and provide power if the AC source is lost.

Figure 8-2 Inverter Operation Status LEDs