Table 6-3 – Xantrex Technology SW Plus 4024 User Manual

Page 154

Advertising
background image

Basic Setup Programming

6–6

976-0043-01-02

Table 6-3 Basic Setup Menu Default Settings for the Sine Wave Plus 5548 Model

Basic Setup Menus

Sine Wave Plus

5548

See Page

Range/
Display

Default

10 Time of Day Setup Menu

See

“10 Time of Day Setup Menu” on page 6–11

for details.

10A Set Hour

00:00:00 to
23:50:00

00:00:00

page 6–11

10B Set Minute

00:00:00 to
00:09:00

00:00:00

page 6–11

10C Set Second

00 to 59

00:00:00

page 6–12

End Menu 10

11 Inverter Setup Menu

See

“11 Inverter Setup Menu” on page 6–12

for details.

11A High Battery Cut Out Vdc

32.2 to 68.0

64.0

page 6–12

11B Low Battery Cut In Vdc

32.2 to 67.8

52.0

page 6–12

11C Low Battery Cut Out Vdc

32.0 to 67.8

44.0

page 6–13

11D LBCO Delay Minutes

01 to 255

15

page 6–13

11E Search Watts (SRCH)

00 to 248

08

page 6–14

End Menu 11

12 Battery Charging Menu

See

“12 Battery Charging Menu” on page 6–19

for details.

12A Finish Stage

SILENT
FLOAT

FLOAT

page 6–19

12B Bulk Volts DC

40.0 to 64.0

57.6

page 6–20

12C Float Volts DC

40.0 to 64.0

53.6

page 6–20

12D Equalize Volts DC

40.0 to 64.0

57.6

page 6–20

12E Max Charge Amps AC

01 to 45

40

page 6–22

12F Bulk Done Amps AC

00 to 50

10

page 6–23

12G EQ Vdc Done Timer

00:00 to
23:50

02:00

page 6–24

12H Max Bulk/EQ Timer

00:00 to
23:50

05:00

page 6–25

12I Temp Comp

LeadAcid
NiCad

LeadAcid

page 6–25

End Menu 12