Table b-6 – Xantrex Technology SW Plus 4024 User Manual

Page 286

Advertising
background image

Configuration Settings

B–12

976-0043-01-02

26G Read LBCO 30 sec Start

LBCO
setting (11C)

22.0

LBCO
setting (11C)

44.0

27 Save/Restore Setup Menu

See

“27 Save/Restore Settings Menu” on page 7–39

for details.

27A Push INV now to save
Settings

Push INV now to save Settings

27B Push GEN to restore settings

Push GEN to restore settings

27C Push GEN for Factory
Defaults

PUSH GEN for Factory Defaults

Table B-5 Advanced Setup Default and User Settings for the Sine Wave Plus 2524 and
2548 Models

Advanced Setup Menus

Sine Wave Plus

2524

Sine Wave Plus

2548

User

Settings

Range/

Display

Default

Settings

Range/

Display

Default

Settings

Table B-6 Advanced Setup Default and User Settings for the Sine Wave Plus 4024 and
4048 Models

Advanced Setup Menus

Sine Wave Plus

4024

Sine Wave Plus

4048

User

Settings

Range/

Display

Default

Settings

Range/

Display

Default

Settings

20 Silent Setup Menu

See

“20 Silent Setup Menu” on page 7–13

for details.

20A Refloat High Volts DC

16.1 to 33.9

28.4

32.2 to 67.8

56.8

20B Refloat Low Volts DC

16.1 to 33.8

25.0

32.2 to 67.8

50.0

20C Float Done Amps AC

00 to 40

10

00 to 40

10

20D Must Float Time Min

00 to 255

05

00 to 255

05

21 Grid AC1 Usage Menu

See

“21 Grid (AC1) Usage Menu” on page 7–16

for details.

21A Grid Usage SB BX

SB BX

SB

SB BX

SB

21B Grid Usage Begin h:m

00:00 to 23:50 21:00

00:00 to 23:50 21:00

21C Grid Usage End h:m

00:00 to 23:50 21:00

00:00 to 23:50 21:00

22 Battery Xfer (BX) Menu

See

“22 Battery Xfer (BX) Menu” on page 7–18

for details.

22A High Xfer (HBX) Vdc

16.1 to 33.9

27.0

32.2 to 67.8

54.0

22B Low Xfer (LBX) Vdc

16.1 to 33.8

23.0

32.2 to 67.8

46.0

23 ALM Relays Menu

See

“23 ALM Relays Menu” on page 7–19

for details.