Multi-Stage Charging Process

The charging cycle uses a multi-stage charging process to maintain the
batteries. Whenever AC power that is within the range of the inverter’s
settings is present at the inverter’s input, it passes power through to the
connected load and begins charging the batteries, indicated by the Bulk or
Float charge indicator LED on the control module.

Figure 6-2 Multi-Stage Battery Charging Process

Bulk Stage

Bulk charge is the first stage in the charging process and provides the
batteries with a controlled, constant current. Once the battery voltage rises
to the bulk voltage threshold, the charger switches to the Absorption
Stage.

Important:

The default settings of the

Sine Wave Plus

may or may not work

for your specific installation. Take the time to review the default settings to make
sure they are appropriate for your installation. If not, you will need to adjust the
settings according to the battery manufacturer’s recommendations. The following
information is provided to help you make the necessary calculations.

Note:

This information is provided for guidance only. Variations in battery

chemistry, as well as, site specific environmental considerations mean that you
should consult your system designer or battery manufacturer for specific
recommendations for appropriate battery voltage and current settings.

If a generator was automatically
started by the inverter to charge

the batteries, it will shut off

when the charger reaches the

FINISH stage after the bulk/

absorption period.

(GENERATOR must be in

AUTO MODE).

Bulk Stage

Absorption Stage

Finish Stage

DC

Voltage

AC

Current

Constant

Current

Reduced

Current

Reduced Current (Float)

Bulk Volts Setting

Float Volts Setting

Time

Max Charge

Amps Setting

Charging

Started

Increased

Voltage

Constant

Voltage

Reduced Voltage

Silent (battery voltage)

BULK DONE AMPS

or

MAX BULK/EQ TIME

No Current (Silent)

Absorption

Time