Connect hot (black) wires, Figure 3-20, Generator input wiring to a single inverter –37 – Xantrex Technology SW Plus 4024 User Manual

Page 119: Figure 3-20, “generator input, Sine wave plus inverter/charger

Advertising
background image

AC Wiring

976-0043-01-02

3–37

b) from the neutral in the generator disconnect to the inverter

NEUTRAL 2 terminal.

3.

Connect HOT (black) wires:

a) from the generator GEN HOT OUT terminal to the circuit

breaker in the generator disconnect, and

b) from the circuit breaker in the generator disconnect to the inverter

AC2 GEN terminal.

4.

Torque all inverter terminal block connections to 25 inch-pounds.

Figure 3-20 Generator Input Wiring to a Single Inverter

AC

GROUND

BAR

(INSIDE)

Sine Wave Plus

Inverter/Charger

Generator

Disconnect Switch

(Optional)

G

N

GROUND

NEUTRAL

GEN HOT OUT

120/240 Vac

GENERATOR

L1

L2

G

HOT OUT

N

HOT IN

1a

2a

3a

Step-down

Autotransformer

(Optional)

2b

3b

3c

AC

GROUND

BAR

(INSIDE)

Sine Wave Plus

Inverter/Charger

AC TERMINAL

BLOCK

IN

V

O

U

T

NEUT

RAL

OUT

NEUT

RAL

2

NEUT

RAL

1

AC1

GRI

D

AC2

GEN

AC TERMINAL

BLOCK

IN

V

O

U

T

NEUT

RAL

OUT

NEUT

RAL

2

NEUT

RAL

1

AC1

GRI

D

AC2

GEN

1c

3d

2c

GROUND

NEUTRAL

GEN HOT OUT

120 Vac ONLY

GENERATOR

G

N

3b

2c

1b

1c

3a

Generator

Disconnect Switch

(Optional)

Generator connections using a
T240, a generator disconnect and
a 120/240 Vac Generator

Generator connections using a
generator disconnect and a
120 Vac Generator