Basic Setup Menu

976-0043-01-02

B–7

12 Battery Charging Menu

See

“12 Battery Charging Menu” on page 6–19

for details.

12A Finish Stage

SILENT
FLOAT

FLOAT

SILENT
FLOAT

FLOAT

12B Bulk Volts DC

20.0 to 32.0

28.8

40.0 to 64.0

57.6

12C Float Volts DC

20.0 to 32.0

26.8

40.0 to 64.0

53.6

12D Equalize Volts DC

20.0 to 32.0

28.8

40.0 to 64.0

57.6

12E Max Charge Amps AC

01 to 30

30

01 to 30

30

12F Bulk Done Amps AC

00 to 30

10

00 to 30

10

12G EQ Vdc Done Timer

00:00 to
23:50

02:00

00:00 to
23:50

02:00

12H Max Bulk/EQ Timer

00:00 to
23:50

05:00

00:00 to
23:50

05:00

12I Temp Comp

LeadAcid
NiCad

LeadAcid

LeadAcid
NiCad

LeadAcid

13 AC Inputs Menu

See

“13 AC Inputs Menu” on page 6–26

for details.

13A Grid (AC1) Amps AC

00 to 60

60

00 to 60

60

13B Gen (AC2) Amps AC

00 to 60

30

00 to 60

30

13C Input Upper Limit Vac

125 to 150

130

125 to 150

130

13D Input Lower Limit Vac

80 to 115

110

80 to 115

110

14 Save/Restore Settings Menu

See

“14 Save/Restore Settings Menu” on page 6–29

for details.

14A Push INV now to save
settings

Push INV now to Save Settings

14B Push GEN to restore settings

Push GEN to restore settings

14C Push GEN for factory
defaults

Push GEN for factory defaults

Table B-3 Basic Setup Default and User Settings for the Sine Wave Plus 4024 and 4048 Models

Sine Wave Plus

4024

Sine Wave Plus

4048

User

Settings

Basic Setup Menus

Range/

Display

Default

Range/

Display

Default