Auxiliary functions

26.2.5.

SPLTRNG – Signal split range

Min. and max. values of the input signal as % for which the valve runs through the entire stroke range.

Factory setting:

Min = 0 %; Max = 100 %

Type.8793: The SPLTRNG auxiliary function can only be selected when operating as a positioner
(position controller).

P.CONTROL = not activated.

Use this auxiliary function to limit the position set-point value range of the Type 8792/8793 by specifying a minimum
and a maximum value.

As a result, it is possible to divide a utilised standard signal range (4 – 20 mA; 0 – 20 mA; 0 – 10 V or 0 – 5 V) into
several devices (without or with overlapping).

This allows several valves to be used alternately or in the case of overlapping set-point value ranges simultane-
ously as actuating element.

EXIT

*

OK

Enter
value

Enter
value

SPLTRNG

Min 0 %

Max 100 %

Input the minimum value of the
input signal as %.
Adjustment range: 0 – 75 %

Input the maximum value of the
input signal as %.
Adjustment range: 25 – 100 %

ENTER

INPUT

INPUT

* If the submenu is left by pressing the

ESC

key, the value remains unchanged.

Figure 62:

Operating structure SPLTRNG

The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key

EXIT

. During the save process, the save

symbol is indicated on the display.

Splitting.a.standard.signal.range.into.two.set-point.value.ranges

4

6

8

10 12 14 16 18 20

100

Valve stroke [%] (

POS)

Set-point value [mA]
(

INP)

Set-point value range

Positioner 1

Set-point value range

Positioner 2

Figure 63:

Graph - SPLTRNG

english

Type 8792, 8793