82

Start-Up

24.

ACTIVATION OF THE PROCESS
CONTROLLER

The process controller is activated by selecting the

P.CONTROL auxiliary function in the ADD.FUNCTION menu.

The activation transfers

P.CONTROL into the main menu (MAIN) where it is available for further settings.

Procedure:

Key

Action

Description

MENU

Press

for approx. 3 s

Switching from process level

setting level.

/

Select

ADD.FUNCTION

ENTER

Press

The possible auxiliary functions are displayed.

/

Select

P.CONTROL

ENTER

Press

P.CONTROL is now marked by a cross .

EXIT

Press

Acknowledgment and simultaneous return to the main menu (MAIN).
P.CONTROL is now activated and incorporated into the main menu.

Table 36:

Activating auxiliary functions

Following activation of

P.CONTROL, the P.Q‘LIN and P.TUNE menus are also available in the main menu

(MAIN). They offer support for the setting of the process control.

P.Q‘LIN Linearization of the process characteristic

Description see Chapter "25.4"

P.TUNE Self-optimization of the process controller (process tune)

Description see Chapter "25.5"

ADD.FUNCTION – Add.auxiliary.functions
Apart from activating the process controller,

ADD.FUNCTION can be used to activate auxiliary functions and

incorporate them into the main menu.

The description can be found in Chapter "26. Configuring the auxiliary functions".