33.4. Configuration of the process data

The following components are required for the configuration:

• Software suitable for the configuration. For example

RSNetWorx for DeviceNet (Rev. 4.12.00).

• ESD file (is on the supplied CD)

Implementation of the configuration process is described in the following chapters

“33.5. Configuration example 1”

and “33.6. Configuration example 2”.

Transmitting.process.data.
To transmit process data via an I/O connection, 5 static input and 2 static output assemblies can be selected.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.

Selecting the process data
The process data is selected by setting the device parameters during initialization of an I/O connection according
to the DeviceNet specification. The following device parameters can be set:

• Active Input Assembly and Active Output Assembly or

• Produced Connection Path and Consumed Connection Path

- if supported by the DeviceNet Master/Scanner -.

33.4.1. Static input assemblies

Name

Address.of.data.attribute.of.the.assemblies.
for.read.access..Class,.Instance,.Attribute

Format.of.the.data.attribute

POS+ERR
(factory setting)

4, 1, 3

Byte 0: POS low
Byte 1: POS high
Byte 2: ERR

POS+CMD+ERR

4, 2, 3

Byte 0: POS low
Byte 1: POS high
Byte 2: CMD low
Byte 3: CMD high
Byte 4: ERR

PV+ERR

4, 3, 3

Byte 0: PV low
Byte 1: PV high
Byte 2: ERR

PV+SP+ERR

4, 4, 3

Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: ERR

PV+SP+CMD+ERR

4, 5, 3

Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: CMD low
Byte 5: CMD high
Byte 6: ERR

Table 119:

Static input assemblies, DeviceNet