91

Start-Up

Operating structure:

*

ENTER

INPUT

INPUT

OK

OK

EXIT

SP-SCALE

SPmin

SPmax

Input upper process set-point
value

Input lower process set-point
value

*

Figure 41:

Operating structure SP-SCALE

Scaling.process.set-point.value.SETUP.→.SP-SCALE:

Key

Action

Description

/

Select

SP-SCALE

ENTER

Press

The submenu options for scaling of the process set-point value are
displayed.

/

Select

SPmin

INPUT

Press

The input screen is opened.

/

Increase value

<–

Select decimal place

Set scaling value (lower process set-point value).

The value is assigned to the smallest current or voltage value of the
standard signal.

OK

Press

Return to

SP-SCALE.

/

Select

SPmax

INPUT

Press

The input screen is opened.

/

Increase value

<–

Select decimal place

Set scaling value (upper process set-point value).

The value is assigned to the largest current or voltage value of the
standard signal.

OK

Press

Return to

SP-SCALE.

EXIT

Press

Return to

SETUP.

Table 42:

SP-SCALE; scaling process set-point value

If the submenu is left by pressing the left selection key

ESC

, the value remains unchanged.

English

Type 8792, 8793

Advertising