130

Auxiliary functions

26.2.14.3. Setting of the submenu options of

OUT BIN 1 / OUT BIN 2

Key

Action

Description

MENU

Press

for approx. 3 s

Switching from process level

setting level.

/

Select

OUTPUT

(To do this, the auxiliary function must be incorporated into the main
menu).

ENTER

The outputs are displayed.

/

Select

OUT BIN1/2

ENTER

Press

Submenu options of

OUT BIN 1/2 are displayed.

Table 58:

OUT BIN1 / OUT BIN2; opening the submenu

POS.Dev.-.Alarm.output.for.excessively.large.control.deviation.of.the.positioner

POS.Lim-1/2 - Output.of.the.current.position.with.respect.to.a.specified.limit.position

Key

Action

Description

POS.Dev - Alarm output for excessively large control deviation of the positioner:

/

Select

POS.Dev

SELEC

Press

The input screen for the limit value

(Deviation:) is opened.

/

Increase value
Reduce value

Input limit value for permitted control deviation.
Adjustment range: 1 ... 50 % (must not be less than the dead band).

OK

Press

Acknowledgment and simultaneous return to the

OUT BIN 1/2 menu.

Then set the required switching status in the

OUT.type submenu.

POS.Lim-1/2 - Output of the current position with respect to a specified limit position:

/

Select

POS.Lim-1/2

SELEC

Press

The input screen for the limit position

(Limit:) is opened.

/

Increase value
Reduce value

Input limit position.
Adjustment range: 0 ... 100 %.

OK

Press

Acknowledgment and simultaneous return to the

OUT BIN 1/2 menu.

Then set the required switching status in the

OUT.type submenu.

Table 59:

OUT BIN1 / OUT BIN2; setting value for POS.Dev or POS.Lim-1/2