Burkert Type 8793 User Manual

Page 87

Advertising
background image

87

Start-Up

25.2.2.1. Effects and dependencies of the settings of

PV-INPUT on

PV-SCALE

The settings in the

PV-SCALE menu have different effects, depending on the signal type selected in

PV-INPUT.
Even the selection options for the units of the process actual value (in

PVmin) depend on the signal

type selected in

PV-INPUT.

See following "Table 39"

Settings.in.the.

submenu.of.

PV-SCALE

Description.of.the.effect

Dependency.on.the.signal.type.selected.in.

PV-INPUT

4 - 20 mA

PT 100

Frequency

PVmin

Selectable unit of the process
actual value for the physical
variables.

Flow rate, temperature,
pressure, length, volume.
(as well as ratio as % and
no unit)

Temperature Flow-rate

Adjustment range:

0 ... 9999
(Temperature -200 ... 800)

-200 ... 800 0 ... 9999

PVmin

PVmax

Specification of the reference range
for the dead band of the process
controller
(

P.CONTROL PID.PARAMETER

DBND).

Yes

Yes

Yes

Specification of the reference range
for the analog feedback (option).
See Chapter "26.2.14. OUTPUT –
Configuring the outputs (option)".

Yes

Yes

Yes

Sensor calibration:

Yes
see "Figure 38"

No

No

K factor

Sensor calibration:

No

No

Yes
see
"Figure 39"

Adjustment range:

0 ... 9999

Table 39:

Effects of the settings in PV-SCALE depending on the signal type selected in PV-INPUT

Example of a sensor calibration for signal type

4 - 20 mA:

Scaling value
[l/min]

Input
signal [mA]

Process set-point
value

Process actual value

4

0

10

20

PVmin

SPmin

PVmax

SPmax

Scaling:

Process actual value from the transmitter:
4 ... 20 mA corresponds to 0 ... 10 l/min

Process set-point value from PLC:
4 ... 20 mA corresponds to 0 ... 8 l/min

Figure 38:

Example of a sensor calibration for signal type 4 - 20 mA

English

Type 8792, 8793

Advertising
This manual is related to the following products: